Status Instruments SEM206TC

SEM206TC Temperature Transmitter for Thermocouples, PC Programmable

The SEM206TC is our entry level PC programmable temperature transmitter. It accepts most common thermocouple sensors and converts the sensor output  to a standard industrial 4 to 20mA transmission signal.

PC configuration allows the user to select range, units and burnout direction, without requiring calibration equipment. Configuration is performed quickly using our new USB port driven configurator by simply connecting two clips to the SEM206TC loop terminals and following the software instructions. Calibration set up may be saved as a file on the PC for later use.

However, if you already know the temperature range you require, we can  configure the product for you at no extra cost.

Features

Suitable for K, J, N, E, T, R, S Thermocouples plus mV
Isolated input to output
Over range LED indication
Programmable burnout
Gost Certificate
Sine Vibration Certificate
Can be supplied fitted to our temperature sensors.

Specifications @ 20°C

INPUT:
Sensor Type: Range °C: Accuracy:
K -200 to 1370 ± 0.1% of F.S. ± 0.5 °C(plus any sensor error)
J -100 to 1200 ± 0.1% of F.S. ± 0.5 °C(plus any sensor error)
E -200 to 1000 ± 0.1% of F.S. ± 0.5 °C(plus any sensor error)
N -180 to 1300 ± 0.1% of F.S. ± 0.5 °C(plus any sensor error)
T -200 to 400 ± 0.2% of F.S. ± 0.5 °C(plus any sensor error)
R -10 to 1760 ± 0.1% of F.S. ± 0.5 °C(plus any sensor error)over range 800 to 1600
S -10 to 1760 ± 0.1% of F.S. ± 0.5 °C(plus any sensor error)over range 800 to 1600
mV -10 to 70 ± 0.02 % of full scale
Isolation: Tested to 250 V dc
Sensor Burnout: Either up or down scale output
Cold Junction: Range (-40 to 85) °C; Accuracy ±0.5 °C Tracking ± 0.05 °C / °C
Stability: Offset 0.15°C / °C Span 0.1°C / °C
OUTPUT:
Output Type: 2 wire, 4 to 20mA current loop.
Output range: 4.0 to 20.0mA
Output Connection : Screw terminal
Maximum output: 21.5mA (in high burnout condition)
Minimum output: 3.8 mA (in low burnout condition)
Accuracy: (mA output /2000) or 5 uA (Which ever is the greater)
Loop Voltage effect: 0.2 uA / V.
Thermal drift: ± 1 uA / °C Typically, ±2 uA / °C Max.
Maximum output load: [(Vsupply-12)/20]K Ohms (Example: 600 Ohms @ 24V)

General Specifications

Update time: 500 ms.
Response Time: 1 second
Start up time: Within 8 seconds ( I out < 4 mA during start up)
Warm-up time: 1 minute to full accuracy
Power Supply : 10 to 30 Volts dc
Ambient operating range: -40 to +85°C [Full Accuracy only between -30 to +75°C].
Ambient storage temperature: -50 to +90°C.
Ambient humidity range: 10 to 90% RH non condensing
Dimensions: 43 mm diameter; 21 mm height.
Weight: 31 g (encapsulated).
APPROVALS:
EMC – BS EN 61326: Electrical equipment for measurement control and laboratory use.
ANNEX A: Immunity test requirements for equipment intended for use in industrial locations
ANNEX F: Test configurations, operational conditions and performance criteria for transducers with integrated or remote signal conditioning.
IEC 61000-4-2: Electrostatic discharge
IEC 61000-4-3: EM Field
IEC 61000-4-4: Transient Burst (output)
IEC 61000-4-5: Surge (output).
Note – Sensor input wires to be less than 3 metres to comply.

Mechanical Drawing

SEM206TC Mechanical Drawing

Electrical Drawing

SEM206TC Wiring Diagram