SEM310 Universal Input HART Temperature Transmitter

Complete with HART Protocol, the SEM310 universal temperature transmitter accepts Pt100, thermocouple, mV and slidewire sensors and can be integrated into systems where the HART protocol is required.

The HART communication protocol allows the user to quickly and easily download information or interrogate the device. It is small in size yet has a performance superior to other larger and more expensive transmitters. A sensor referencing facility enables the transmitter to be accurately matched to a particular sensor.

Features

HART Protocol
Universal Input
Accepts Pt100, Thermocouple & Slidewire Sensors
Sensor Burnout Detect
Input, Output Isolation
Gost Certificate
Sine Vibration Certificate
ATEX Approved Version

Specifications @ 20°C

INPUT RTD (Pt100):
Sensor Range: -200 to 850°C
Minimum Span: 25 °C
Linearisation: BS-EN60751BS1904DIN43760JISC 1604custom
Basic Measurement Accuracy: 0.01 % FRI ± 0.07 % rdg
INPUT THERMOCOUPLE:
Sensor Type: Sensor Range °C
K 200 to 1370
J -200 to 1200
E -200 to 1000
N -180 to 1300
T -210 to 400
R -10 to 1760
S -10 to 1760
L -100 to 600
Basic Measurement Accuracy: 0.04% FRI ± 0.04% rdg or 0.5°C (whichever is greater)
Linearisation BS EN 60584-01, BS 4937, IEC 584-1
INPUT MILLIVOLTS
Input: Voltage Source
Range: -10 to 75mV
Characterisation: Linear, Custom
Basic Measurement Accuracy: ±10 µV ±0.07 % rdg
INPUT SLIDEWIRE:
Input: 3 wire potentiometer
Resistance Range: 10 to 390Ω
Characterisation: Linear, Custom
Basic Measurement Accuracy: 0.1 %
OUTPUT:
Output Range: 4 to 20mA, Min. 3.75mA, Maximum 21.5mA.
Supply Voltage: 10 to 40V
Output Connection : Screw terminal
Accuracy: ±5µA

General Specifications

Input/Output Breakdown Isolation: 500V AC rms
Time Constant (Filter off): 0.5 s (to 90 % of final value) Filter Factor Off/selectable between 1 s and 32 s or Adaptive
Warm up: 120 s to full accuracy
Ambient operating temperature: -40 to +85°C
Ambient storage temperature: -50 to +85°C
Ambient humidity range: 10 to 95% RH non condensing
Dimensions: 44mm diameter; 24mm height
APPROVALS:
EMC: BS EN 61326.
ATEX: II 1G EExia IIC T4-T6.
FM (IS Version): FM3610-IS/I/1/ABCD/T4.

Mechanical Drawing

SEM310 Mechanical Drawing

Electrical Drawing

SEM310 Wiring Connections

Hazardous Area Installation

SEM310 Hazardous Area Connections